Selection Procedure

STEP 1 System flow rate (GPM) of hot liquid
STEP 2 :: Heat transfer requirement = input energy lost to heat 1 HP = 2545 BTU/HR
:: Performance curves based on Inlet Temperature Difference (ITD) of 50°F ITD = (Inlet temperature of hot liquid) - (Ambient temperature of air)
:: If ITD is not 50°F: Heat transfer requirement = Input energy lost to heat x 50°F
STEP 3 Select curve for heat exchanger model at or above heat transfer requirement

Fin Cool® performance charts based on air velocity of 1000 feet per minute (fpm) through the heat exchanger core. If air velocity is not 1000 fpm, multiply heat transfer requirement calculated in step 2 by tabulated multiplier before using performance curves:

  500 fpm 1000 fpm 1500 fpm 2000 fpm
Air Velocity Multiplier 1 ROW - Style A 1.2 1 0.9 0.8
Air Velocity Multiplier 2 ROW - Style B/C 1.3

Plotted pressure drop (PSID) values based on viscosity of 50 SSU. If viscosity is not 50 SSU, multiply PSID value by tabulated multiplier to obtain estimate of actual PSID:
  50 SSU 100 SSU 150 SSU 200 SSU

250 SSU

PSID Multiplier 1 1.75 2.3 2.75 3.2

See for general heat transfer information.

 
Dimensional Data

Figure letter refers to the diagrams above. Dimensions are in inches. Performance Curve # refers to the Performance Charts below.

 
 
Performance Charts

Heat transfer performance based upon 50°F ITD and 1000 FPM air velocity. See Selection Procedure for sizing heat exchanger.
Pressure Drops Indicated
5 PSID 10 PSID 15 PSID 20 PSID
 
 
 